Start, Stop, Run Speed by Keypad Operation
Copyright © 2008 Francis J. Martino
Parameter / Set Keypad Display to read
Notes
DRV-03 / Keypad
Press FWD, REV, STOP/RESET Keys on Keypad to Start, Stop Drive
DRV-04 / Keypad-1
DRV-00 / 0.00 to 60.00 Hz
Desired Frequency of operation
Press PROG Button, Set the desired frequency, Press ENTER key.
Output Frequency will change when ENTER key is pressed.
OR
DRV-04 / Keypad-2
DRV-00 / 0.00 to 60.00 Hz
Desired Frequency of operation
Press PROG Button, Press Up Arrow to increase speed, speed increases immediately.
Press Down Arrow to decrease speed, speed decreases immediately.
When desired speed is reached, press ENTER to write new value into memory.
FU-1 / Run prev.
/None Forward and Reverse keys are enabled
/Forward Prev Forward run key is disabled
/Reverse Prev Reverse run key is disabled
The following Parameter settings are for all "common" applications. Factory
default settings may be changed as necessary.
Parameter / Set Keypad Display to read
Notes
DRV-00 / Cmd. Freq/Out Curr
Program: Command (Run) Frequency when in PROG mode.
Read Only: Command Frequency when in STOP
Read Only: Output Frequency/Output Current during Run
DRV-01 / Acc. time
Factory Default: 20.0 sec
DRV-02 / Dec. time
Factory Default: 30.0 sec
DRV-12 / Fault Code
Read only.
Fault codes are given in the Instruction Manual
FU1-29 / Line Frequency
Factory Default: 60.00 Hz
FU1-30 / Maximum Frequency
Factory Default: 60.00 Hz
FU1-31 / Base Frequency
Factory Default: 60.00 Hz
FU1-32 / Start Frequency
Factory Default: 0.50 Hz
FU1-49 / VAC 440V
Factory Default: 100.0%
Set at 104.5% for 460 VAC at the motor terminals
Set at 109.1% for 480 VAC at the motor terminals
FU1-50 / Motor Volt 0 V
Factory Default: 0.00
Set at motor nameplate rating: 200, 230 or 460.
FU2-40 to FU2-45 / Motor HP, Poles, Slip, FLA Current, No-load Current, Efficiency
FU2-46 / Load Inertia
Set at 0 for load inertia less than 10 times that of motor inertia
Set at 1 for load inertia at about 10 times that of motor inertia
|