VT = Variable Torque (Fan or Centrifugal Pump Load),
110% Overload for 1 minute
CT = Constant Torque (Machinery or Positive Displacement Pump Load),
150% Overload for 1 minute
Sensorless Vector
V/F Ratio: Linear, Square, User V/F
PID or Direct Acting 4 to 20 mA, 0 to 10 VDC
Keypad on cover
ModBus RTU is Standard
UL Listed
Options available at additional cost:
Enclosed Drives:
Stainless Steel, Fiberglass, Water Proof, UL Type 4/12 and 3R
Bypass - Two Contactor or Three Contactor Equivalent
AC Line Reactor - Nominal 3% or 5%
Output Reactor
dv/dt Output Filter
Industrial Lightning Arrestor/Surge Supressor (Models LA-302, LA-603)
Dynamic Braking Units and Resistors
RS-485, DeviceNet, N2, ProfiBus, BACnet, LonWorks
Remote mounting kit for Keypad (2, 3, or 5 meter cable)
Speed Potentiometer on cover
Application Notes:
A 3 % Line Reactor will reduce incoming power by 3%. Thus 480 VAC will be reduced
to a nominal 465 VAC.
A 5% Line Reactor will reduce incoming power by 5%. Thus 480 VAC will be reduced
to a nominal 456 VAC.
Use an Output Reactor for motor lead lengths of 50 to 100 feet.
Use a dV/dT Output Filter for motor lead lengths over 125 feet.
For over 750 feet advise of motor lead length and cable size.