1 Phase, 3 HP (maximum HP of 3 Phase motor in single phase power applications)
24 Full Load Amps output maximum
200-230 VAC (-15%, +10%), 50-60 Hz (+/- 5%)
Standard features with P-Series Drive:
Variable Frequency Drive
Rated for Variable Torque
UL Type 3R Enclosure reduces thermal absorption with white, solar
reflective finish. (Type 3R: Outside use to provide a degree of
protection against falling rain; undamaged by the formation of ice
on the enclosure.)
Rated for 92 degrees F outside temperature, non-direct sunlight
Attain up to 110 degress F outside temperature, non-direct sunlight
by de-rating the VFD
PID Control
Energy efficiency via Sleep Mode which turns off the pump and
non-essential drive functions when no demand is present.
Contines to monitor system set point while in sleep mode.
ModBus RTU
Internal Filtered Cooling Fan
A single VFD has the capability to control up to four additional pump
starters, VFDs, or soft starters in lead-lag operation, reducing
the need for additonal conrols.
Accepts sensor inputs of 0-10 VDC and 4-20 mA analog signals.
Provides additional 12 VDC and 24 VDC power for sensors.
Dual PID control with Pre-PID mode and time delay reduces water
hammer and cavitation.
Available options at additional cost:
Broken Pipe Alarm and Shut Down
Anti-cycling Protection in low consumption applications
3% Line Reactor
5% Line Reactor
Lightning Arrestor
Load Reactor
dv/dt Output Filter
Bypass
Panel Heater (30W) with Thermostat
Passive Harmonic Filter
Door Mounted Controls:
Drive Run Pilot Light (Type 12 and 3R, Green)
Drive Fault Pilot Light (Type 12 and 3R, Red)
Drive Off Pilot Light (Type 12 and 3R, Red)
Hand-Off-Auto Switch
Speed Potentiometer
Door Mounted Keypad
Door Mounted Keypad with Clear Cover (Type 4X rated)
User Defined Nameplate
Disconnect
Communications Cards:
RS485
DeviceNet
N2
ProfiBus DP
BACnet
LonWorks
A 3 % Line Reactor will reduce incoming power by 3%. Thus 480 VAC will be reduced to
a nominal 465 VAC.
A 5% Line Reactor will reduce incoming power by 5%. Thus 480 VAC will be reduced to
a nominal 456 VAC.
Use an Output Reactor for motor lead lengths of 50 to 100 feet.
Use a dV/dT Output Filter for motor lead lengths over 125 feet.
For over 750 feet of motor lead length advise of motor lead length and cable size.