3 Pole, 150 Amp,
Model CMS-150/K
120 VAC, 60 Hz coil,
2NO/2NC Aux Contacts,
Non-reversing,
Panel Mount,
UL Listed,
AC3 Rating @ 440V = 150 Amp,
IEC Rated,
Tested by Cerus Industrial and passed NEMA Size 4 rating
Overload Relay:
Adjustable Amperage Range: 65 to 100 Amps
Three Phase
40 HP @ 200 VAC
50 HP @ 230 VAC
100 HP @ 460 VAC
100 HP @ 575 VAC
Single Phase
15 HP @ 115 VAC
25 HP @ 230 VAC
Dimensions in mm: 260.4 H x 120 W x 157 D
The Overload Relay has the following specifications:
Class 10A
Bi-metallic Model CTK
Ambient Compensated over the range of -5 to 40 degrees C
Operational temperatures: -25 to 40 degrees C
1NO/1NC overload contacts
Manual/Automatic reset
Differential Current / Phase Failure protection
Visible Trip Indication
Adjustable motor amp trip range.
Overload heaters are not necessary.
Warranty:
Contactor 5 Years
Overload Relay 18 Months
|