| Combination Starter with Motor Circuit Protector Disconnect NEMA Size 0 Contactor, 18 Amps Overload Relay, adjustable from 4.4 to 22 Amps
30kAIC @ 460VAC
Normal shipment is one to two business days. Allow additional time for transit.
Motor Horsepower and Voltage must be specified with your order for proper Motor Circuit Protector selection. Type HP and Voltage into "Comments" section as you enter the order or call (203) 217-2353
Three Phase
3 @ 200 VAC
5 @ 230 VAC
10 HP @ 460 VAC
15 HP @ 575 VAC
Single Phase
1 @ 115 VAC
3 HP @ 230 VAC
Model ISS , Type 1 Enclosure, Steel Enclosure, UL Listed Combination Starter with Motor Circuit Protector Disconnect, Contactor, Overload Relay Start, Stop Pushbuttons Control Power Transformer, 208/240/277/480 Primary 120 or 575 Primary is also available
The Model CRP Electronic Overload Relay will be included and has the following features: Adjustable Trip Amps Class 1 to 30 Overload selection Protections:
Phase reversal Phase current unbalance Phase loss/phase failure Stall Protection
Phase reversal trips within 1 second
Phase current unbalance: trips within 5 seconds when the phase current unbalance exceeds 50%.
Phase loss/phase failure: trips within 3 seconds when phase current is 70% unbalanced.
Stall Protection: Trips at 170% of full load amps at 3 seconds.
|