| Combination Starter with
Motor Circuit Protector Disconnect
NEMA Size 00 Contactor, 9 Amps
Overload Relay, adjustable from 1 to 5 Amps
65kAIC @ 460VAC
Normal shipment is one to two business days. Allow additional time for transit.
Motor Horsepower and Voltage must be specified with your order for proper Motor Circuit Protector selection. Type HP and Voltage into "Comments" section as you enter the order or call (203) 217-2353
Three Phase
1/2 HP @ 200 VAC
1/2 HP @ 230 VAC
1 HP @ 460 VAC
1.5 HP @ 575VAC
Single Phase
Advise of motor full load amps @ 115 VAC
1/6 HP @ 230 VAC
Model ISS ,
Type 4/12 Enclosure, Steel Enclosure,
UL Listed
Combination Starter with Motor Circuit Protector Disconnect,
Contactor,
Overload Relay
Start, Stop Pushbuttons
Control Power Transformer, 208/240/277/480 Primary
120 or 575 Primary is also available
The Model CRP Electronic Overload Relay will be included and has the following features:
Adjustable Trip Amps
Class 1 to 30 Overload selection
Protections:
Phase reversal
Phase current unbalance
Phase loss/phase failure
Stall Protection
Phase reversal trips within 1 second
Phase current unbalance: trips within 5 seconds when the phase current unbalance exceeds 50%.
Phase loss/phase failure: trips within 3 seconds when phase current is 70% unbalanced.
Stall Protection: Trips at 170% of full load amps at 3 seconds.
|