| Description: |
Contactor:
Model MRC-18-120VAC
3 Pole, 18 Amp,
120 VAC, 60 Hz coil,
(Optional coil volts for 60 Hz: 208, 277, 480, 600)
(Optional coil volts for 50/60 Hz: 24, 48, 110, 120, 220, 240, 380, 400, 440, 500, 550)
(Optional coils for DC Volts: 12, 24, 48, 100, 110, 125, 200, 250)
Non-reversing,
1 NO/NC Auxiliary Contact,
Panel Mount or DIN rail,
UL Listed
AC1 Rating (Resistive Load) = 40 Amp
AC3 Rating @ 200 to 240 V = 18 Amp
AC3 Rating @ 380 to 440 V = 18 Amp
AC3 Rating @ 500 to 550 V = 13 Amp
Three Phase
5 HP @ 200 VAC
5 HP @ 230 VAC
10 HP @ 460 VAC
10 HP @ 575 VAC
Single Phase
1 HP @ 115 VAC
3 HP @ 230 VAC
Overload Relay:
Shipped loose for customer mounting to contactor.
Model MTK-32-18
Adjustable Amperage Range: 12 to 18 Amps
Class 10
Ambient Compensated over the range of -5 to 40 degrees C
Operational temperatures: -25 to 40 degrees C
1NO/1NC overload contacts
Manual/Automatic reset
Differential Current / Phase Failure protection
Visible Trip Indication
Adjustable motor amp trip range.
Overload heaters are not necessary.
|