Other drives available:
0.5 to 3 HP, 230 VAC 1 Phase input, 230 VAC 3 Phase output
0.5 to 5 HP, 200-230 VAC 3 Phase input, 230 VAC 3 Phase output
0.5 to 5 HP, 380-480 VAC 3 Phase input, 480 VAC 3 Phase output
Note: The only electrical equipment that will operate successfully on power
derived from a variable frequency drive is a three phase electric motor.
Variable Frequency Drives with an Explosion Proof Enclosure
Available from 0.5 to 2 HP, 240 or 480 VAC.
3 HP and above is available for use with customer supplied positive ventilation.
Options:
Enclosed Drives:
Stainless Steel, Fiberglass, Water Proof
Circuit Breaker Disconnect
Service Entrance Rated Circuit Breaker Disconnect
Bypass - Two Contactor or Three Contactor Equivalent
AC Line Reactor - Nominal 3% or 5%
Output Reactor
dv/dt Output Filter
Industrial Lightning Arrestor/Surge Supressor (Models LA-302, LA-603)
Dynamic Braking Units and Resistors
Passive Harmonic Filter
Application Notes:
A 3 % Line Reactor will reduce incoming power by 3%. Thus 480 VAC will be
reduced to 465 VAC.
A 5% Line Reactor will reduce incoming power by 5%. Thus 480 VAC will be
reduced to 456 VAC.
Use an Output Reactor for motor lead lengths of 50 to 100 feet.
Use a dV/dT Output Filter for motor lead lengths over 125 feet.
For over 750 feet advise of motor lead length and cable size.
Programming of the iP5A Drive:
Features of the iP5ADrive:
Drive operation may be programmed to change from PID Control to Constant Speed
by switching at the terminals.